Induced Losses in Three-core SL-type High Voltage Cables
It is considered that the present IEC 60287 standard overestimates the induced losses in SL-type armored cables, which are commonly used to connect offshore windfarms to the onshore grid. This paper addresses the issue through a series of equivalent-circuit models for the estimation of circulating-c...
Main Authors: | , , , |
---|---|
Format: | Article |
Language: | English |
Published: |
2015-06-01.
|
Subjects: | |
Online Access: | Get fulltext |
Summary: | It is considered that the present IEC 60287 standard overestimates the induced losses in SL-type armored cables, which are commonly used to connect offshore windfarms to the onshore grid. This paper addresses the issue through a series of equivalent-circuit models for the estimation of circulating-current, eddy-current, and armor losses in these cables. Finite-element models are used for further validation. Both the finite-element and the equivalent-circuit models use an equivalent-material representation of the armor layer, for which two calculation methods are developed. The results demonstrate clearly that the equation for armor loss in such cables as presently used in IEC standards is overly conservative. |
---|