Quantifying possible transmission network benefits from higher cable conductor temperatures

The maximum current rating of high voltage power cables is limited by the allowable conductor temperature, in order to prevent damage to the adjacent dielectric material. Cross-linked polyethylene dielectrics are generally subject to a thermal limit of 90°C in the UK. The use of novel new dielectric...

Full description

Bibliographic Details
Main Authors: Pilgrim, J.A (Author), Lewin, P.L (Author), Gorwadia, A. (Author), Waite, F. (Author), Payne, D. (Author)
Format: Article
Language:English
Published: 2013-06.
Subjects:
Online Access:Get fulltext
Description
Summary:The maximum current rating of high voltage power cables is limited by the allowable conductor temperature, in order to prevent damage to the adjacent dielectric material. Cross-linked polyethylene dielectrics are generally subject to a thermal limit of 90°C in the UK. The use of novel new dielectric materials may allow this temperature limit to be raised considerably. This paper examines the possible thermal rating benefits available from 400kV cable systems capable of conductor temperatures of up to 150°C in a number of common deployment scenarios, including direct burial and installation in ventilated tunnels. The results of the analysis show a divide between modest improvements in continuous rating and much more utilizable gains in short term emergency ratings which could offer the possibilities of single cable circuits being able to match the current carrying capacity of overhead lines over 24hr periods.