Improving Stability by Enhancing Critical Fault Clearing Time

The Bulk Electric System (BES) in the United States includes transmission lines of 100kV and above, transformers of 100kV and above on Low Voltage (LV) side and generating units that step up to 100 kV and above. The BES is a power network that connects different states and utility companies via tie...

Full description

Bibliographic Details
Main Author: Ghani, Ammara M.
Format: Others
Published: Scholar Commons 2019
Subjects:
Online Access:https://scholarcommons.usf.edu/etd/7793
https://scholarcommons.usf.edu/cgi/viewcontent.cgi?article=8990&context=etd
id ndltd-USF-oai-scholarcommons.usf.edu-etd-8990
record_format oai_dc
spelling ndltd-USF-oai-scholarcommons.usf.edu-etd-89902019-11-22T10:12:29Z Improving Stability by Enhancing Critical Fault Clearing Time Ghani, Ammara M. The Bulk Electric System (BES) in the United States includes transmission lines of 100kV and above, transformers of 100kV and above on Low Voltage (LV) side and generating units that step up to 100 kV and above. The BES is a power network that connects different states and utility companies via tie lines for exchange of Power. To maintain the integrity of power systems, it is very important to keep the BES intact and for that the regulatory authority, North American Electric Reliability Corporation (NERC), has developed over 100s of reliability standards and is responsible to enforce them. During the past several years, the U.S has experienced power system instability events in which a fault occurred on one part of a system and travelled through the entire interconnection. Some of the extreme events are a major concern for power systems in the U.S that consists of Cascading, Uncontrolled Separation and natural disasters damaging the transmission circuits. Protection System plays important role towards the stability of power systems, but most important aspect of protection system is the Critical Fault Clearing Time. This case study focused on the Critical Fault Clearing Time enhancement by making a comparison between a Gang Operated (GO) and Independent Pole Operated (IPO) Breaker. An extreme event was considered as a fault scenario for the case study that consisted of three phase fault followed by breaker failure scenario. PSS®E 33.9 software was used to perform dynamic study on three different power plants to show the comparison between GO breaker and IPO breaker. A tremendous improvement was achieved using IPO breaker with more than 100% increase in Critical Fault Clearing Time. 2019-06-25T07:00:00Z text application/pdf https://scholarcommons.usf.edu/etd/7793 https://scholarcommons.usf.edu/cgi/viewcontent.cgi?article=8990&context=etd Graduate Theses and Dissertations Scholar Commons 3 phase fault Breaker Failure Extreme event Gang Operated breaker Independent Pole Operated breaker Instability Electrical and Computer Engineering
collection NDLTD
format Others
sources NDLTD
topic 3 phase fault
Breaker Failure
Extreme event
Gang Operated breaker
Independent Pole Operated breaker
Instability
Electrical and Computer Engineering
spellingShingle 3 phase fault
Breaker Failure
Extreme event
Gang Operated breaker
Independent Pole Operated breaker
Instability
Electrical and Computer Engineering
Ghani, Ammara M.
Improving Stability by Enhancing Critical Fault Clearing Time
description The Bulk Electric System (BES) in the United States includes transmission lines of 100kV and above, transformers of 100kV and above on Low Voltage (LV) side and generating units that step up to 100 kV and above. The BES is a power network that connects different states and utility companies via tie lines for exchange of Power. To maintain the integrity of power systems, it is very important to keep the BES intact and for that the regulatory authority, North American Electric Reliability Corporation (NERC), has developed over 100s of reliability standards and is responsible to enforce them. During the past several years, the U.S has experienced power system instability events in which a fault occurred on one part of a system and travelled through the entire interconnection. Some of the extreme events are a major concern for power systems in the U.S that consists of Cascading, Uncontrolled Separation and natural disasters damaging the transmission circuits. Protection System plays important role towards the stability of power systems, but most important aspect of protection system is the Critical Fault Clearing Time. This case study focused on the Critical Fault Clearing Time enhancement by making a comparison between a Gang Operated (GO) and Independent Pole Operated (IPO) Breaker. An extreme event was considered as a fault scenario for the case study that consisted of three phase fault followed by breaker failure scenario. PSS®E 33.9 software was used to perform dynamic study on three different power plants to show the comparison between GO breaker and IPO breaker. A tremendous improvement was achieved using IPO breaker with more than 100% increase in Critical Fault Clearing Time.
author Ghani, Ammara M.
author_facet Ghani, Ammara M.
author_sort Ghani, Ammara M.
title Improving Stability by Enhancing Critical Fault Clearing Time
title_short Improving Stability by Enhancing Critical Fault Clearing Time
title_full Improving Stability by Enhancing Critical Fault Clearing Time
title_fullStr Improving Stability by Enhancing Critical Fault Clearing Time
title_full_unstemmed Improving Stability by Enhancing Critical Fault Clearing Time
title_sort improving stability by enhancing critical fault clearing time
publisher Scholar Commons
publishDate 2019
url https://scholarcommons.usf.edu/etd/7793
https://scholarcommons.usf.edu/cgi/viewcontent.cgi?article=8990&context=etd
work_keys_str_mv AT ghaniammaram improvingstabilitybyenhancingcriticalfaultclearingtime
_version_ 1719295210476797952