Summary: | 碩士 === 吳鳳科技大學 === 消防研究所 === 106 === This study is aimed at the employees and visitors of the National K Museum. This dynamic firefighting plan was developed and verified according to the technical manual of fire safety and performance of buildings. The evacuation time in the room is safely verified in the 5F C area showroom. Assuming the setting of mechanical smoke exhaust equipment, the occupancy density of 4.15 persons per square meter of the room, the time required for the room to complete the refuge is 2.896 min > the time for the smoke falling in the room is 2.895 min, appears as a dangerous situation of human life. In the case of this mechanical smoke exhaust device, the maximum occupancy density of persons is 2.93 persons/square meter.In the safety verification of the evacuation time of entire building, the 4F office B406 fire statrs, the top floor to set up mechanical smoke exhaust equipment, according to the model of fire growth in t2.
Once the maximum occupancy density of each room is more than 3.74 people / square meter, then The time required to complete the evacuation is 29.06 min > the fall time of the smoke in the room is 28.99 min, which will result in a life-threatening situation. In this way, it can serve as a reference for the largest number of people admitted to the National Museum of Marine Science and Technology.
Keywords: National K Museum, fire drills, safe time for evacuation time
|