Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer

博士 === 國立臺北科技大學 === 電機工程系研究所 === 100 === This dissertation presents a successful mitigation experience of ferroresonance (FR) with a Damping Reactor(DR) involving electromagnetic type Potential Transformers(PTs) of a 161 kV Gas Insulated Switchgear(GIS) in Taiwan. PTs have a typically low thermal ca...

Full description

Bibliographic Details
Main Authors: Pei-Yu Cheng, 鄭沛昱
Other Authors: Kuo-Hsiung Tseng
Format: Others
Language:en_US
Published: 2012
Online Access:http://ndltd.ncl.edu.tw/handle/x7s9xu
id ndltd-TW-100TIT05442080
record_format oai_dc
spelling ndltd-TW-100TIT054420802019-05-15T20:51:53Z http://ndltd.ncl.edu.tw/handle/x7s9xu Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer 161 kV電磁感應型比壓器鐵磁共振分析、量測及抑制方法 Pei-Yu Cheng 鄭沛昱 博士 國立臺北科技大學 電機工程系研究所 100 This dissertation presents a successful mitigation experience of ferroresonance (FR) with a Damping Reactor(DR) involving electromagnetic type Potential Transformers(PTs) of a 161 kV Gas Insulated Switchgear(GIS) in Taiwan. PTs have a typically low thermal capacity and high accuracy due to their measuring functions. Low core losses are necessary to obtain high accuracy, but they also reduce its damping ability and therefore increase the possibility of FR. FR happened twice and destroyed PTs for just nine months in the study case. Complete FR waveforms of 161 kV PT were obtained via field tests never conducted before in Taiwan. The first field test had a reappearing FR which sustained up to 22.9 seconds in 11 random operations and the second to fourth field tests confirmed the validity of DR which shortened FR less than 4.36 seconds in 29 random operations which are carried out in thermal power plant, hydro power plant and nuclear power plant. A reliable prediction by EMTP/ATPDraw simulation and a useful mitigation method with a proper DR were proved by both field tests and the following 23 months satisfactory operations for 82 times which extracted from SCADA system in a thermal power plant since Nov., 2008. The five years study would prove valuable for further research in higher voltage level GIS. Although the first paper on FR was published in 1920, FR is still not a fully understood phenomenon. This dissertation focuses on single phase FR in GIS with PT, fed by the circuit breaker grading capacitance. In principle, FR is a forced oscillation in a nonlinear series resonance circuit including a capacitance and nonlinear inductance, which shows significantly distorted voltage and current waveforms. The complex nonlinear behavior of the saturable inductance can cause fundamental FR, subharmonic FR, quasi-periodic and even chaotic oscillations. FR can result in high overvoltage and high overcurrent, which can finally damage the high voltage equipment or PTs due to dielectric and thermal problems. Even if there is the risk of ferroresonance for specific GIS configurations, electromagnetic PTs are used rather than capacitive ones because of their reliability, higher accuracy and stable transformation ratio during the entire lifetime. However, combine the theory, GIS and PT maker’s experiences, this dissertation provides an overview of network configurations, parameters influencing the FR behavior and a number of methods to avoid or suppress FR are discussed. A very comprehensive analysis is performed by detailed modeling using time domain simulation with a digital computer transient analysis program such as the EMTP/ATPDraw and compares them with field tests and measurements. It would be valuable on planning and designing for electrical engineers. Kuo-Hsiung Tseng 曾國雄 2012 學位論文 ; thesis 190 en_US
collection NDLTD
language en_US
format Others
sources NDLTD
description 博士 === 國立臺北科技大學 === 電機工程系研究所 === 100 === This dissertation presents a successful mitigation experience of ferroresonance (FR) with a Damping Reactor(DR) involving electromagnetic type Potential Transformers(PTs) of a 161 kV Gas Insulated Switchgear(GIS) in Taiwan. PTs have a typically low thermal capacity and high accuracy due to their measuring functions. Low core losses are necessary to obtain high accuracy, but they also reduce its damping ability and therefore increase the possibility of FR. FR happened twice and destroyed PTs for just nine months in the study case. Complete FR waveforms of 161 kV PT were obtained via field tests never conducted before in Taiwan. The first field test had a reappearing FR which sustained up to 22.9 seconds in 11 random operations and the second to fourth field tests confirmed the validity of DR which shortened FR less than 4.36 seconds in 29 random operations which are carried out in thermal power plant, hydro power plant and nuclear power plant. A reliable prediction by EMTP/ATPDraw simulation and a useful mitigation method with a proper DR were proved by both field tests and the following 23 months satisfactory operations for 82 times which extracted from SCADA system in a thermal power plant since Nov., 2008. The five years study would prove valuable for further research in higher voltage level GIS. Although the first paper on FR was published in 1920, FR is still not a fully understood phenomenon. This dissertation focuses on single phase FR in GIS with PT, fed by the circuit breaker grading capacitance. In principle, FR is a forced oscillation in a nonlinear series resonance circuit including a capacitance and nonlinear inductance, which shows significantly distorted voltage and current waveforms. The complex nonlinear behavior of the saturable inductance can cause fundamental FR, subharmonic FR, quasi-periodic and even chaotic oscillations. FR can result in high overvoltage and high overcurrent, which can finally damage the high voltage equipment or PTs due to dielectric and thermal problems. Even if there is the risk of ferroresonance for specific GIS configurations, electromagnetic PTs are used rather than capacitive ones because of their reliability, higher accuracy and stable transformation ratio during the entire lifetime. However, combine the theory, GIS and PT maker’s experiences, this dissertation provides an overview of network configurations, parameters influencing the FR behavior and a number of methods to avoid or suppress FR are discussed. A very comprehensive analysis is performed by detailed modeling using time domain simulation with a digital computer transient analysis program such as the EMTP/ATPDraw and compares them with field tests and measurements. It would be valuable on planning and designing for electrical engineers.
author2 Kuo-Hsiung Tseng
author_facet Kuo-Hsiung Tseng
Pei-Yu Cheng
鄭沛昱
author Pei-Yu Cheng
鄭沛昱
spellingShingle Pei-Yu Cheng
鄭沛昱
Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
author_sort Pei-Yu Cheng
title Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
title_short Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
title_full Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
title_fullStr Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
title_full_unstemmed Ferroresonance Analysis, Measurement and Suppression Methodsof 161 kV Electromagnetic Potential Transformer
title_sort ferroresonance analysis, measurement and suppression methodsof 161 kv electromagnetic potential transformer
publishDate 2012
url http://ndltd.ncl.edu.tw/handle/x7s9xu
work_keys_str_mv AT peiyucheng ferroresonanceanalysismeasurementandsuppressionmethodsof161kvelectromagneticpotentialtransformer
AT zhèngpèiyù ferroresonanceanalysismeasurementandsuppressionmethodsof161kvelectromagneticpotentialtransformer
AT peiyucheng 161kvdiàncígǎnyīngxíngbǐyāqìtiěcígòngzhènfēnxīliàngcèjíyìzhìfāngfǎ
AT zhèngpèiyù 161kvdiàncígǎnyīngxíngbǐyāqìtiěcígòngzhènfēnxīliàngcèjíyìzhìfāngfǎ
_version_ 1719106104779079680