Summary: | 碩士 === 國立臺北科技大學 === 能源與冷凍空調工程系碩士班 === 97 === Pumps in the current methods of measurement, mainly『CNS665』 test announced by general law, in order to establish water saving performance measurement and verification methods, In this study, the actual cases, respectively, for the fixed-frequency, frequency and the pump impeller to amend the case, for data analysis, evaluation and the establishment of the performance of air conditioning experience model circulating water pump in order to build water pump project to improve the energy efficiency of the verification process with the theoretical model calculation. The purpose of this study is the use of particles were carried out in baseline algorithm model, so that the regression coefficient calculated with the actual consumption of electricity to improve the error can be reduced by the actual results show that the average pump frequency error rate for the 0.79%, water pump impeller to amend the average error rate of 1.67 percent and the average pump frequency rate of 12.93 percent error in the establishment of the three different types of improvements, mainly in order to provide for future energy-saving performance in the water pump to ensure the implementation of the improvement project way of reference.
|