Fault Ride through Capability of Off-shore Wind Farm
碩士 === 國立中山大學 === 電機工程學系研究所 === 95 === Large off-shore wind farms raise the concern of widespread tripping of off-shore wind generator in the presence of system faults and corresponding voltage dips that could potentially cause system wide blackout. In this thesis an offshore wind farm and three dif...
Main Authors: | , |
---|---|
Other Authors: | |
Format: | Others |
Language: | zh-TW |
Published: |
2007
|
Online Access: | http://ndltd.ncl.edu.tw/handle/gt38hk |
Summary: | 碩士 === 國立中山大學 === 電機工程學系研究所 === 95 === Large off-shore wind farms raise the concern of widespread tripping of off-shore wind generator in the presence of system faults and corresponding voltage dips that could potentially cause system wide blackout. In this thesis an offshore wind farm and three different types of power transmission are modeled and studied using simulation software. Off-shore wind farm composed of fixed speed induction generators and HVAC interconnection, HVAC interconnection plus STATCOM and HVDC interconnections are studied. Onshore grid faults are simulated for each interconnection. Voltage tolerance curves are established to assess fault ride through capability of each interconnection and compared with different grid transmission ride through capacity required by grid operator.
|
---|