The Effect Analysis and Simulation Test of Harmonics on Differential Protection of Special Transformers

碩士 === 中原大學 === 電機工程學系 === 88 === All the of high speed railway systems around the world use single phase voltage to the trains. Because of the large variations of electric power when starting and breaking the trains, there arises a lot of harmonics in the system. The nonlinear load may cause a lot...

Full description

Bibliographic Details
Main Authors: Tsung Ling Tsou, 鄒宗龍
Other Authors: Jin-Maun Ho
Format: Others
Language:zh-TW
Published: 2000
Online Access:http://ndltd.ncl.edu.tw/handle/75702761655663144858
Description
Summary:碩士 === 中原大學 === 電機工程學系 === 88 === All the of high speed railway systems around the world use single phase voltage to the trains. Because of the large variations of electric power when starting and breaking the trains, there arises a lot of harmonics in the system. The nonlinear load may cause a lot of harmonics, too. These affect the power quality and may misoperate the protection relays. The research aims at the effects of harmonic to the differential protecting special transformer. The CA type differential relay is used to protect the special transformer, and the Scott transformer is selected. Different combinations of harmonics are need for testing. A relationship between the tripping time of the differential relay and the harmonics quantity are found. We expect the results will be helpful and useful to the applications of differential relays to special transformer.