Risk of thermal pollution of the Danube passing through Serbia due to thermal power plants
A thermal power plant (TPP) uses large amounts of fresh water, mostly for cooling purposes. Among different types of cooling systems, once-through cooling is the most water-intensive and has the greatest environmental impacts. From the view-point of the steam cycle efficiency, this type of...
Main Authors: | , , , , |
---|---|
Format: | Article |
Language: | English |
Published: |
VINCA Institute of Nuclear Sciences
2018-01-01
|
Series: | Thermal Science |
Subjects: | |
Online Access: | http://www.doiserbia.nb.rs/img/doi/0354-9836/2018/0354-983618323L .pdf |
Summary: | A thermal power plant (TPP) uses large amounts of fresh water, mostly for
cooling purposes. Among different types of cooling systems, once-through
cooling is the most water-intensive and has the greatest environmental
impacts. From the view-point of the steam cycle efficiency, this type of
cooling still provides the most efficient electricity production, and
therefore is widely used. Water is withdrawn from nearby water bodies,
absorbs heat from the steam in a condenser, and then discharged back to its
original source at higher temperatures causing severe environmental impacts,
including fish killing, disturbing ecosystems, and heating-up natural water
bodies. The total installed capacity of almost 1100 MW on the right bank of
the Danube in Serbia threatens the ecosystem of this large international
river due to thermal pollution. This problem will be even more pronounced in
the near future, due to an inevitable increase in production capacity for new
350 MW, currently under construction. Herein, analysis of the legal framework
for the protection of water from thermal pollution as well as analysis of the
actual situation on the site of the TPP “Kostolac” in Serbia are presented.
Based on meteorological and hydrological parameters, configuration and
operation parameters of the plant, the numerical simulation of the condenser
was carried on. The temperature of the water leaving condenser and amount of
heat discharged back to the river are obtained. According to those results,
the analysis of the existing thermal pollution of the Danube River in the
flow through Serbia is given by numerical simulation using software ANSYS
CFX. Analysis of thermal discharge into the Danube for the five-year period
has been carried out. The cooling water effluent causes a temperature
increase in the area of the right bank of the Danube, and this thermal
disturbance extends along the right river bank for kilometers. Note that the
flow rate of the Danube is currently large enough to compensate this thermal
disturbance, but for a smaller river and/or larger electricity production
capacities, this influence would have even more significant consequences on
the ecosystem, making those results even more useful for further analysis. |
---|---|
ISSN: | 0354-9836 2334-7163 |