Application of Battery Energy Storage Systems for Relief of Generation Curtailment in Terms of Transient Stability

Maintaining transient stability is crucial in power system operation. Transient stability is mainly affected by the generation amount of the study region, as well as the transmission topology. Several countermeasures can be taken for transient stability, but the usually used control means are genera...

Full description

Bibliographic Details
Main Authors: Hyeongpil Bang, Dwi Riana Aryani, Hwachang Song
Format: Article
Language:English
Published: MDPI AG 2021-06-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/14/13/3898
Description
Summary:Maintaining transient stability is crucial in power system operation. Transient stability is mainly affected by the generation amount of the study region, as well as the transmission topology. Several countermeasures can be taken for transient stability, but the usually used control means are generating unit tripping and generation curtailment. In terms of economic operation, one can say that the solution of generating unit tripping is more beneficial. To maintain the transient stability of the east coast region in the Korean power system, applying generation curtailment in the normal state is further needed, because the required tripping amount is too large for the case of only taking generator tripping, and this might cause a critical decrease in system frequency, possibly resulting in operation of the first stage of under frequency relay (UFR). This paper presents the application of battery energy storage systems (BESSs) to relieve the generation curtailment, using the characteristic of fast response of BESS. Assuming that BESSs are installed in the candidate location in the study region, the adequate BESS action of absorbing the kinetic energy from those critical generators after disturbances can improve transient stability, and it can decrease the amount of generation curtailment. This paper includes the results of simulation studies to show the effectiveness of the BESS control for the relief of generation curtailment.
ISSN:1996-1073