The Correlation of Transformer Oil Electrical Properties with Water Content Using a Regression Approach

An experimental investigation is conducted to measure and correlate the impact of the water content on the electrical characteristics of the mineral oil for transformers, particularly the breakdown voltage, the resistivity, and the dielectric dissipation factor. Regression method is carried out to c...

Full description

Bibliographic Details
Main Authors: Sifeddine Abdi, Noureddine Harid, Leila Safiddine, Ahmed Boubakeur, Abderrahmane (Manu) Haddad
Format: Article
Language:English
Published: MDPI AG 2021-04-01
Series:Energies
Subjects:
Online Access:https://www.mdpi.com/1996-1073/14/8/2089
Description
Summary:An experimental investigation is conducted to measure and correlate the impact of the water content on the electrical characteristics of the mineral oil for transformers, particularly the breakdown voltage, the resistivity, and the dielectric dissipation factor. Regression method is carried out to compare the results obtained through laboratory experiments with those predicted using an analytical model. A treatment to reduce water content in oil involving filtration, degassing and dehydration using a SESCO mobile station was applied to the new, regenerated, and used oil samples in service. The breakdown voltage, the resistivity, and the dielectric dissipation factor of the samples were measured. Regression analysis using an exponential model was applied to examine the samples electrical properties. The results show that, after treatment, the breakdown voltage and resistivity increase as the water content decreases, unlike the dielectric dissipation factor which exhibits a decreasing trend. This trend is found to be similar for the three oil samples: new, regenerated, and used. The results of the regression analysis give close agreement with the experimental results for all the samples and all studied characteristics. The model shows strong correlation with high coefficients (>90%).
ISSN:1996-1073