Summary: | China is actively promoting ocean territory construction, and how to design low-energy buildings to fit the unique climate of tropical island regions has received much attention. The heat transfer coefficient of a building external surface plays a vital role in calculating air-conditioning load accurately. To obtain reasonable heat transfer coefficients in the tropical island region, this study introduced a naphthalene sublimation experiment to conduct full-scale measurements on convective heat transfer coefficients (CHTCs) in the tropical island region, and proposed a simplified calculation model of evaporative heat transfer coefficients (EHTCs). Results indicated that the function expression between CHTC and wind speed was CHTC = 5.56 + 4.48u (R2 = 0.94), and it was validated to be reliable. Furthermore, compared with CHTCs and radiation heat transfer coefficients (RHTCs), the EHTC had a wider changing range, owing to rainfall effects. Moreover, whether evaporation was considered or not, the difference of total heat transfer coefficients (THTCs) on building external surfaces was 5.2 W/(m2·K) for the whole year, so evaporation cannot be ignored directly. Additionally, THTCs with consideration of evaporation in winter and summer were 33.4 W/(m2·K) and 38.9 W/(m2·K) severally, which are much larger than the recommended values in the Chinese standard. This study would make up for the lack of surface heat transfer coefficients in energy conservation design of tropical island buildings.
|