Analysis and location of Turn-To-Turn short circuit of rotor windings in generator
With the increase of generator running time, the probability of generator rotor problems increases constantly. In this paper, a generator is taken as an example. During maintenance, the generator is found to have the evidence of turn-to-turn short circuit of rotor windings by the repetitive surge os...
Main Authors: | , |
---|---|
Format: | Article |
Language: | English |
Published: |
EDP Sciences
2021-01-01
|
Series: | E3S Web of Conferences |
Online Access: | https://www.e3s-conferences.org/articles/e3sconf/pdf/2021/09/e3sconf_iaecst20_04018.pdf |
Summary: | With the increase of generator running time, the probability of generator rotor problems increases constantly. In this paper, a generator is taken as an example. During maintenance, the generator is found to have the evidence of turn-to-turn short circuit of rotor windings by the repetitive surge oscilloscope method, which is verified by the AC impedance power loss test of the rotor winding. The position of turn-to-turn short circuit is determined by the inter-pole voltage method and the coil voltage method. The accuracy of the test method is further verified by the generator rotor’s return repair. |
---|---|