Seawater reverse osmosis membrane fouling causes in a full scale desalination plant; through the analysis of environmental issues: raw water quality
Background: Membrane clogging is one of the most important problem for desalination plant operators in Iran, therefore, this study was conducted to investigate the main causes of this problem using field analysis. Methods: In this study, six continuous membranes in a reverse osmosis (RO) pressure...
Main Authors: | , , , |
---|---|
Format: | Article |
Language: | English |
Published: |
Kerman University of Medical Sciences
2020-07-01
|
Series: | Environmental Health Engineering and Management |
Subjects: | |
Online Access: | http://ehemj.com/article-1-624-en.html |
Summary: | Background: Membrane clogging is one of the most important problem for desalination plant operators
in Iran, therefore, this study was conducted to investigate the main causes of this problem using field
analysis.
Methods: In this study, six continuous membranes in a reverse osmosis (RO) pressure vessel under the
33-month service period (April 2017 to November 2019) were selected. The membranes were analyzed
through visual evaluation of the outer and inner membrane surface, analyzing the damages and physical
harms, oxidative stress tests, iron spot test, fouling chemical analysis using loss on ignition (LOI) tests,
X-ray fluorescence (XRF), and Fourier-transform infrared (FTIR) spectroscopy.
Results: Particle size distribution in raw seawater (EC = 55 000 μs/cm, turbidity = 11 NTU) was 66.4%
smaller than 1 μ and 28.3% between 1 to 1.9 μm. Physical damages were not seen on the membranes but
telescopic damages were observed which was due to membrane fouling. Removal efficiencies of turbidity
and silt density index (SDI) were 84% and 18%, respectively. Membrane oxidation was also seen. Most
of the sediments compositions on the membranes were SiO2, Al2O3, MgO, and Fe2O3. Biological fouling
was detected on the membranes surface.
Conclusion: Inaccurate use of chlorine neutralizer caused the residual chlorine to be present in the
membrane entering water, which damaged the membrane. Accumulation of clogging agents on
membrane surface showed malfunction of pretreatment function, therefore, revision of design and
operation of units is necessary. Biological fouling is due to non-effective pre-chlorination of drinking
water. Metallic compounds sedimentation on the membrane is due to improper use of anti-fouling
chemicals. High SDI in the influent shows the need to change the cartridge filters. |
---|---|