Effect of duration of the pause single-phase auto-reclosing on electro-power transmission capacitance

This paper discusses the problem associated with accidents in the aerial line (AL) ultra-high voltage (UHV) due to its big length. In lines with a voltage of 500-1150 kV the overwhelming proportion of trips (98%) is caused by single-phase short circuit (SPSC). A substantial portion (70%) single-phas...

Full description

Bibliographic Details
Main Authors: Krasil'nikova Tatyana, Jononaev Saiyod
Format: Article
Language:English
Published: EDP Sciences 2017-01-01
Series:E3S Web of Conferences
Online Access:https://doi.org/10.1051/e3sconf/20172501009
Description
Summary:This paper discusses the problem associated with accidents in the aerial line (AL) ultra-high voltage (UHV) due to its big length. In lines with a voltage of 500-1150 kV the overwhelming proportion of trips (98%) is caused by single-phase short circuit (SPSC). A substantial portion (70%) single-phase short circuits is erratic arc accidents which can be successfully eliminated in a high-speed auto-reclosing (HSAR) or single-phase auto-reclosing (SPAR). Success single-phase auto-reclosing (SPAR) at liquidation by single-phase short circuit (SPSC), on the one hand, is determined by the characteristics of the secondary arc current, and on the other hand the effectiveness of ways to reduce secondary arc current and recovery voltage development. The minimum dead time, at a HSAR it is usually taken as 0.5 s., at single-phase autoreclosing (SPAR) it depends on the current value of the arc support is in the range of 0.5-3.0 s. The article shows high efficiency of use single-phase auto reclosing (SPAR) at liquidation SPSC in a single-chain AL voltage of 500 kV, the dependence of the bandwidth of transmission in maintaining the dynamic stability from the length of the pause SPAR.
ISSN:2267-1242