Summary: | Grid-connected photovoltaic (PV) inverters are gaining attention all over the world. The optimal controller setting is key to the successful operation of a grid-connected PV system. In this paper, a novel plant propagation algorithm-based fractional order proportional-integrator (FOPI) controller for cascaded DC link voltage and inner current control of a grid-connected PV controller has been proposed, which outperforms particle swarm optimization-based PI and elephant herding optimization-based FOPI in terms of multicriteria-based analysis. The performance of the proposed controller also has been measured in terms of total harmonic distortion to maintain the appropriate power quality. Also, the proposed controllers were tested under various solar irradiance and voltage sag conditions to show the effectiveness and robustness of the controllers. The whole system is developed in OPAL-RT using MATLAB/Simulink and RT-LAB as a machine-in-loop (MIL) system to validate the performance in real time.
|